Availability: | |
---|---|
BMS HS-16S150A-20A
HelithTech
Product Description
Functional Features
Highly Integrated Analogue Front End
Isolated Power Supply Circuit
Integrated Serial Port IC
High Voltage Accuracy (≤10mV)
High Current Accuracy (≤2%@FS)
4-Way Battery Temperature Detection (≤2°C)
SOC Estimation Function
SOH Estimation Function
Short Circuit Protection Function
Adjustable Over-Current Protection
Multiple Sleep And Wake-Up Modes
Low Power Consumption
RS485 Communication
Adjustable Parameter Settings
Data Refresh Interval (Period) ≤ 2 Seconds
LED Status Indication Function
Charge Equalization Function
SOC Accuracy (≤5% @ 50% Capacity Range Or More)
Functional Block Diagram
Parameters
No. | Indicator Items | Factory Default Parameters | Is It Possible To Set | Remarks | |
1 | Monomer Overcharge Protection | Monomer Overcharge Alarm Voltage | 3600mV | settable | monomer overcharge protection value is inconsistent with mobile default value |
Monomer Overcharge Protection Voltage | 3650mV | settable | |||
Monomer Overcharge Protection Delay | 1.0S | settable | |||
Monomer Overvoltage Protection Disengaged | Release Voltage of Monomer Overcharge Protection | 3380mV | settable | ||
Capacity Release | SOC≤94% | settable | |||
Discharge Release | discharge current > 1A | ||||
2 | Monomer Over-Discharge Protection | Monomer Over-Discharge Warning Voltage | 2700mV | settable | after 30 seconds of over-discharge protection, if it cannot be recovered, it will enter low power mode |
Monomer Over-Discharge Protection Voltage | 2500mV | settable | |||
Monomer Over-Discharge Protection Delay | 1.0S | settable | |||
Monomer Over-Discharge Protection Disengaged | Release Voltage of Monomer Over-Discharge Protection | 2750mV | settable | ||
Release When Charging | activated by connecting to the charger | ||||
3 | Total Overcharge Protection | Total Overcharge Warning Voltage | 57.6V | settable | |
Total Overcharge Protection Voltage | 58.4V | settable | |||
Total Overcharge Protection Delay | 1.0S | settable | |||
Total Overvoltage Protection Disengaged | Release Voltage of Total Overcharge Protection | 54V | settable | ||
Capacity Release | SOC≤94% | settable | |||
Discharge Release | discharge current > 1A | ||||
4 | Total Over-Discharge Protection | Total Over-Discharge Warning Voltage | 43.2V | settable | after 30 seconds of over-discharge protection, if it still cannot be recovered, it will enter low power mode. |
Total Over-Discharge Protection Voltage | 40V | settable | |||
Total Over-Discharge Protection Delay | 1.0S | settable | |||
Total Over-Discharge Protection Disengaged | Release Voltage of Total Over-Discharge Protection | 44V | settable | ||
Release When Charging | can be activated by connecting to a charger | ||||
5 | Charging Overcurrent Protection | Charging Overcurrent Warning Current | 75A | settable | the state will be locked after 3 consecutive occurrences and will not be automatically unlocked. |
Charging Overcurrent Protection Current | 80A | settable | |||
Charging Overcurrent Protection Delay | 1.0S | settable | |||
Charging Overcurrent Protection Disengaged | Automatic Release | Automatic release after 2min | |||
Discharge Release | Discharging current > 1A | ||||
6 | Discharging Overcurrent 1 Protection | Alarm Current of Discharging Overcurrent 1 | 160A | settable | the state will be locked after 3 consecutive occurrences and will not be automatically unlocked. |
Protection Current of Discharging Overcurrent 1 | 170A | settable | |||
Protection Delay of Discharging Overcurrent 1 | 1.0S | settable | |||
Discharging Overcurrent 1 Protection Disengaged | Automatic Release | Automatic release after 2min | |||
Charge Release | Charging current > 1A |
7 | Discharge Overcurrent 2 | Protection Current of Discharging Overcurrent 2 | ≥180A | settable | the state will be locked after 1 occurrence and will not be automatically unlocked. |
Protection Delay of Discharging Overcurrent 2 | 100mS | settable | |||
Discharge Overcurrent 2 Protection Disengaged | Automatic Release | Automatic release after 2min | |||
Charge Release | Charging current > 1A | ||||
8 | Short Circuit Protection | Short Circuit Protection | Yes | ||
Short Circuit Protection Disengaged | Short-circuit protection will be disengaged when charging is available. | ||||
Short-circuit protection will be automatically lifted when the load is removed. | |||||
9 | MOS High Temperature Protection | Temperature Value of MOS High Temperature Warning | 90°C | settable | |
Temperature Value of MOS High Temperature Protection | 110°C | settable | |||
Release Temperature of MOS Protection | 90°C | settable | |||
10 | Cell Temperature Protection | Temperature Value of Charging Low Temperature Warning | 3°C | settable | |
Temperature Value of Charging Low Temperature Protection | 0°C | settable | |||
Release Temperature of Charging Low Temperature Protection | 3°C | settable | |||
Temperature Value of Charging High Temperature Warning | 55°C | settable | |||
Temperature Value of Charging High Temperature Protection | 60°C | settable | |||
Release Temperature of Charging High Temperature Protection | 55°C | settable | |||
Temperature Value of Discharge Low Temperature Warning | -10°C | settable | |||
Temperature Value of Discharge low temperature protection | -20°C | settable | |||
Release Temperature of Discharge Low Temperature Protection | 0°C | settable | |||
Temperature Value of Discharge High Temperature Warning | 55°C | settable | |||
Temperature Value of Discharge High Temperature Protection | 60°C | settable | |||
Release Temperature of Discharge High Temperature Protection | 50°C | settable | |||
11 | Ambient Temperature Alarms | Temperature Value of Ambient Low Temperature Warning | -10°C | settable | |
Temperature Value of Ambient Low Temperature Protection | -20°C | settable | |||
Release Temperature of Ambient Low Temperature Protection | 0°C | settable | |||
Temperature Value of Ambient High Temperature Warning | 60°C | settable | |||
Temperature Value of Ambient High Temperature Protection | 65°C | settable | |||
Release Temperature of Ambient High Temperature Protection | 55°C | settable | |||
12 | Current Consumption | Self-Consumption Current During Operation | ≤25mA | ||
Low Power Mode Current | ≤200μA | ||||
13 | Equalization Function | The Voltage When The Equalization Function is Turned On | 3400mV | settable | High differential pressure between monomers |
The Differential Pressure When The Equalization Function is Turned On | 30mV | settable | Equalization should not be activated at 1V. | ||
14 | Capacity Default Setting | Low Battery Alarm | SOC <20% | settable | No alarms when charging. |
15 | Hibernation Function | Sleeping Voltage | 2500mV | settable | |
Delay Time | 1h | settable | |||
16 | Cell Failure Protection | Monomer Differential Pressure | Differential Pressure > 800mV | settable (300mV- (800mV) | No charging or discharging allowed |
17 | Full Charge Judgement | Full Charge Voltage | 57.6V | ||
Cut-off Current | 2A |